Epoxy resin cast dry-type transformer

10kV SC(B)12(13.14.18)
The SC(B)12(13,14,18) series epoxy resin cast dry-type transformers can be used as new generation products of oil- immersed distribution transformers. They are the best among various dry-type transformers and especially suitable for important places such as urban power gids, high-rise buildings, business centers, theaters, hospitals, hotels, tunnels, subways, stations, wharves, airports, underground power stations, laboratories and combined substations.
Quantity
Contact Now
add to cart
      The SC(B)12(13,14,18) series epoxy resin cast dry-type transformers can be used as new generation products of oil- immersed distribution transformers. They are the best among various   dry-type transformers and especially suitable for important places such as urban power gids, high-rise buildings, business centers, theaters, hospitals, hotels, tunnels, subways, stations, wharves, airports, underground power stations, laboratories and combined substations.

Product Features:

    The SC(B)12(13,14,18) power transformers produced by us are low-noise, low-loss and resin    cast coil dry-type transformers with product model certificates issued earlier in China. With  advanced design, high-quality materials, scientific formula, strict process and high-standard  testing, the products have the following characteristics:

  1. The HV winding is wound with copper wire, and the LV winding is wound with copper wire or copper foil. DMD is filled and wrapped. Under vacuum state, it is cast with epoxy resin without filler. After curing, a solid oblong shape is formed, with high mechanical strength, small partial discharge and high reliability.
  2. They are flame retardant, explosion-proof and environmentally friendly. Insulating  materials such as DMD have self- extinguishing characteristics and will not generate arc due to short circuit, and the resin will not produce toxic and harmful gases under high heat.
  3. The coil does not absorb moisture, and the core clamp has a special anti-corrosion  protective layer. The products can operate in 98% relative humidity and other harsh  environments, without the need of dehumidification treatment for intermittent operation.
  4. They have high resistance to short circuit and lightning impulse.
  5. The resin layer inside and outside the coil is thin and has good heat dissipation  performance. Natural air cooling (AN) is generally adopted. Transformers of any IP grade  can be equipped with an air cooling system (AF) to improve the short-time overload capacity and ensure safe operation.
  6. They realize low loss, good power saving effect, economical operation and free maintenance.
  7. They are characterized by small size, light weight, less occupied space, and low installation cost. There is no need to consider oi discharge tank, fire prevention facilities and standby power supply.
Since there is no risk of fire or explosion, they can be dispersedly installed in the load center and sufficiently close to the power consumption point,thus reducing the line cost and  saving the cost of expensive LV facilities.

◆Technical  parameter  table   for  SC(B)12(NX3)Dry-type  non-excitation  voltage  distribution  transformer

 
Rated capacity
(kVA)
voltage combination
and tapping range
connection symbol
No-load current (%)
No-load loss
(W)
load loss at different insulation levels (W)
Short Circuit impedance
(%)
High Voltage(KV)
HVtapping
range
(%)
Lowvo
Ltage
(KV)
130℃(B)
(100℃)
155℃(F)
(120℃)
180℃(H)
(145℃)
30
6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4
Dyn11 Yyn0
2.4
150
670
710
760
4.0
50
2.4
215
940
1000
1070
80
1.8
295
1290
1380
1480
100
1.8
320
1480
1570
1690
125
1.6
375
1740
1850
1980
160
1.6
430
2000
2130
2280
200
1.4
495
2370
2530
2710
250
1.4
575
2590
2760
2960
315
1.2
705
3270
3470
3730
400
1.2
785
3750
3990
4280
500
1.0
930
4590
4880
5230
630
1.0
1070
5530
5880
6290
630
1.0
1040
5610
5960
6400
6.0
800
1.0
1215
6550
6960
7460
1000
1.0
1415
7650
8130
8760
1250
1.0
1670
9100
9690
10370
1600
1.0
1960
11050
11730
12580
2000
0.8
2440
13600
14450
15560
2500
0.8
2880
16160
17170
18450
1600
1.0
1960
12280
12960
13900
8.0
2000
0.8
2440
15020
15960
17110
2500
0.8
2880
17760
18890
20290
  

◆ Technical parameter table for SC(B)13 Dry-type non-excitation voltage distribution transformer

Rated capacity
(kVA)
voltage combination
and tapping range
connection symbol
No-load current (%)
No-load loss
(W)
load loss at different insulation levels (W)
Short Circuit impedance
(%)
High Voltage(KV)
HVtapping
range
(%)
Lowvo
Ltage
(KV)
130℃(B)
(100℃)
155℃(F)
(120℃)
180℃(H)
(145℃)
30
6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4
Dyn11 Yyn0
2.4
135
605
640
685
4.0
50
2.4
195
845
900
965
80
1.8
265
1160
1240
1330
100
1.8
290
1330
1415
1520
125
1.6
340
1560
1665
1780
160
1.6
385
1800
1915
2050
200
1.4
445
2130
2275
2440
250
1.4
515
2330
2485
2660
315
1.2
635
2940
3125
3350
400
1.2
705
3370
3591
3850
500
1.2
835
4130
4390
4700
630
1.0
965
4970
5290
5660
630
1.0
935
5050
5365
5760
6.0
800
1.0
1095
5890
6265
6710
1000
1.0
1275
6880
7315
7880
1250
1.0
1505
8190
8720
9330
1600
1.0
1765
9940
10555
11300
2000
0.8
2195
12200
13005
14000
2500
0.8
2590
14500
15455
16600
1600
0.1
1765
11000
11660
12500
8.0
2000
0.8
2195
13500
14360
15400
2500
0.8
2590
15900
17000
18200

◆ Technical  parameter  table   for  SC(B)14(NX2) Dry-type  non-excitation  voltage  distribution  transformer

Rated capacity
(kVA)
voltage combination
and tapping range
connection symbol
No-load current (%)
No-load loss
(W)
load loss at different insulation levels (W)
Short Circuit impedance
(%)
High Voltage(KV)
HVtapping
range
(%)
Lowvo
Ltage
(KV)
130℃(B)
(100℃)
155℃(F)
(120℃)
180℃(H)
(145℃)
30
6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4
Yyn0 Dyn11
2.0
130
605
640
685
4.0
50
2.0
185
845
900
965
80
1.5
250
1160
1240
1330
100
1.5
270
1330
1415
1520
125
1.3
320
1565
1665
1780
160
1.3
365
1800
1915
2050
200
1.1
420
2135
2275
2440
250
1.1
490
2330
2485
2665
315
1.0
600
2945
3125
3355
400
1.0
665
3375
3590
3850
500
1.0
790
4130
4390
4705
630
0.85
910
4975
5290
5660
630
0.85
885
5050
5365
5760
6.0
800
0.85
1035
5895
6265
6715
1000
0.85
1205
6885
7315
7885
1250
0.85
1420
8190
8720
9335
1600
0.85
1665
9945
10555
11320
2000
0.70
2075
12240
13005
14005
2500
0.70
2450
14535
15445
16605
 
 
         ◆ Technical parameter table for SC(B)18(NX1) Dry-type non-excitation voltage distribution transformer
 
Rated capacity
(kVA)
voltage combination
and tapping range
connection symbol
No-load current (%)
No-load loss
(W)
load loss at different insulation levels (W)
Short Circuit impedance
(%)
High Voltage(KV)
HVtapping
range
(%)
Lowvo
Ltage
(KV)
130℃(B)
(100℃)
155℃(F)
(120℃)
180℃(H)
(145℃)
30
6
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4
Yyn0 Dyn11
2.0
105
605
640
685
4.0
50
2.0
155
845
900
965
80
1.5
210
1160
1240
1330
100
1.5
230
1330
1415
1520
125
1.3
270
1565
1665
1780
160
1.3
310
1800
1915
2050
200
1.1
350
2135
2275
2440
250
1.1
415
2330
2485
2665
315
1.0
510
2945
3125
3355
400
1.0
570
3375
3590
3850
500
1.0
670
4130
4390
4705
630
0.85
775
4975
5290
5660
630
0.85
750
5050
5365
5760
6.0
800
0.85
875
5895
6265
6715
1000
0.85
1020
6885
7315
7885
1250
0.85
1205
8190
8720
9335
1600
0.85
1415
9945
10555
11320
2000
0.70
1760
12240
13005
14005
2500
0.70
2080
14535
15445
16605
 
 
 
epoxy resin cast dry-type transformer,dry-type transformer,epoxy resin transformer,cast resin dry-type transformer,cast resin transformer,distribution dry-type transformer,10kV dry-type transformer,35kV dry-type transformer,dry-type transformer manufacturer.